621-2100RC
6212100RC

115VAC Output 8-pt


line

The 'R' suffix indicates the module can be removed or inserted into an I/O rack while the rack remains powered. Other I/O modules in the rack continue to control the machine or process.
A "C" suffix indicates models that conform to CE directives 73/23IEEC, the low voltage directive, and 89/336IEEC, the EMC directive.

621-2100RC
Outputs8
Output On at zero crossing
Points Per
Common
4
Nominal Voltage115 VAC
Voltage Range90-140 VAC
Maximum
Current Range
2 A/circuit,
6 A/common,
8 A/module
Surge Current15 A for 2 cycle
(non-repetitive)
Off-State
Leakage Current
<=5 mA (typical)
On-State
Voltage Drop
<=2 Vdc at 2 A
Fusing1 A circuit
3 A slo-blo
Operating Current
+5 Vdc
80 mA plus 24 mA
for each energized
output, 272 mA max
Terminal Block
Required
621-9949