621-6650R

Availability: Low Stock


Availability: Low Stock

Output Module 48VDC

Power Derating
Applications requiring voltages of more than 48VDC may require derating according to the ambient temperature (60 degC maximum) of the rack.

CAUTION
--- Exceeding the recommended number of ON outputs may damage the module.
---Applications requiring voltages of more than 48VDC should not operate above 140 degF (60 degC), or damage may occur to components.


621-6650R
Outputs16
Points Per

module
16
Voltage Range38-66 Vdc
Maximum

Current Range
2A per circuit,

5A per group

of 4, 12A permodule
Surge Current8 A for 10ms
Field Power

Requirement
25 mA for each

energized output
Off-State

Leakage Current
<=5 mA (typical)
On-State

Voltage Drop
<=2 Vdc at 2 A