621-6700
No Immediate Stock, Request Availability
120VDC Source Output 8-pt
NUMBER OF OUTPUTS ........ 8 per module
POINTS PERCOMMON ..........4
VOLTAGE RANGE .............90-130 VDC
MAX. CURRENT RANGE ........0.5A
SURGE CURRENT .............4A for 10ms (non-repetitive)
FIELD POWER REQUIREMENT ..........7mA at 120VDC for each energized output
OFF-STATE LEAKAGE CURRENT ........<= 5mA (typical)
ON-STATE VOLTAGE DROP...........<= 2VDC at 2A
MODULE OPERATING CURRENT +5VDC..... 70mA plus 5mA for each energized output, 110mA (max.)
TERMINAL BLOCK REQUIRED........ 621-9949
NOTE
Terminals T1 and B1 supply voltage connections for circuits 1 through 4. Terminals T2 and B2 supply
voltage connections for circuits 5 through 8. Separate voltage sources may power circuits 1 through 4 and 5
through 8 if the factory-installed jumpers are removed.