621-6650R
Availability: Low Stock
Output Module 48VDC
Power Derating
Applications requiring voltages of more than 48VDC may require derating according to the ambient temperature (60 degC maximum) of the rack.
CAUTION
--- Exceeding the recommended number of ON outputs may damage the module.
---Applications requiring voltages of more than 48VDC should not operate above 140 degF (60 degC), or damage may occur to components.
| 621-6650R | |
|---|---|
| Outputs | 16 |
| Points Per module | 16 |
| Voltage Range | 38-66 Vdc |
| Maximum Current Range | 2A per circuit, 5A per group of 4, 12A permodule |
| Surge Current | 8 A for 10ms |
| Field Power Requirement | 25 mA for each energized output |
| Off-State Leakage Current | <=5 mA (typical) |
| On-State Voltage Drop | <=2 Vdc at 2 A |